SMS-box

icon-support-sms-box

icon-support-sms-box

Support for SMS-box temperature monitor and alarm.
(no longer produced) 


What is the connection sequence for the PT100 inputs:

Brown +
White –
Green-
 


System – Diagnosis, does not see MASTER unit.
 

Unit name incorrectly spelled, may not contain any spaces or punctuation marks.
Example:
incorrect: ‘ SMS-box 1’
correct ‘ SMSbox1 ‘


Measurement value not stable, wobbles a few degrees.

Unit is sensitive to poor EARTHING.
Use protected power and sensor cables, and connect earth of 230V well.


Unit1 is good, Unit2 does not work.

a. Forgot to execute menu ‘Read in data’ after logging in. As a result data from box1 programmed in box2. Program after all remembers data from the last reading out!
b. Incorrect name (with spaces) set; set back to for example ‘SMSbox2′.
c. Waited too long with logging in -must be done within 15 sec.- results in incorrect communication.
Unit started again, within 15 sec. logged in, name changed, set back setting manually to box2.
 


How can you give your measurement value in an SMS message?

Use the button ‘Insert Analogue value’ when formulating the message.
See also HELP, enter Messages.
 


how can you give the text ‘High alarm’ or ‘ Low alarm’ in the alarm message?

Enter a message. For High or Low notification simply create two messages with the relevant alarm limits High or Low. See also HELP, enter Messages.
 


how can you remotely reset an alarm?
Call by telephone and enter #pincode#.
See also HELP, confirming alarm.
 


how can I view the settings without changing them?

On computer select:
-PC log in
-Read in Data
and then view the data in the various windows.
Do NOT press the Program button!
 


what do the LEDs of the modem mean?
DTR: Data terminal ready, modem switched on
DCD: Data Carrier Detect, connection with the SMS central set up. Approx. 1 min. on when sending SMS.
RX: Receive data, flashes briefly when receiving data
TX: Transmit data, flashes briefly when sending data.
 


Downloads
-installation package reading out software v2.10

-manual SMS-box

Regiemaster-280

icon-rm280-data logger

icon-rm280-data logger

-REMARK: This product is out of produktion-    
this page is for reference only

Digital recorder for the encoded internal storage of a maximum of 8 measurement inputs. Via the built-in adjustable alarm contacts the measurement values can also be monitored. The saved measurement values and process recordings can then be shown or printed as graph or in table form.

DESCRIPTION

The Regiemaster data logger is an 8-channel digital recorder that independently and automatically saves the measurement values in the internal memory, after which they can be viewed via a computer in table form or graph. The data logger also has two alarm contacts with which various adjustable monitoring functions can be realised.  The saved measurement values can be transferred to the computer via an RS232 connection or a CompactFlash memory card. All settings can be modified via the computer or on the unit itself. As the measurement data is stored encoded it cannot be changed afterwards and so can function as evidence.

SPECIFICATIONS
Types Regiemaster-280: Digital 8 channels measurement values recorder.
Description Data logger with 8 identical measurement channels. Each channel can be set individually if required. See supplements. Housing 144x72mm for panel installation according to DIN43700. LCD display 2×16 characters with background lighting. RS232 connection for communication with computer. RS485 bus for connecting several Regiemasters. Relay contacts N.O. for Alarm functions and Sensor Error. The RM280 is supplied complete with mounting and connection components, power module 230V-24Vdc, DIN-rail connector block for connecting measurement signals, RS232 cable. Software for reading out and displaying measurement values and setting parameters.Software suitable for MS-Windows 95/98/2000/XP. All connections with screw/insert connectors. Delivered including connection and mounting materials.
Possible applications
  • Process monitoring/control.
  • HACCP control.
  • Registering Cooling transport.
  • Controling temp/%RH in homes.
Measurement system As requested with order: PT100 – IEC60751/3-lead Voltage or current inputs.
Measurement range Available in various types of measurement inputs, standard 8 identical input ranges. These can be modified per channel with a certain range:

  • PT100 range e.g. -50.0…+50.0°C, 0.0…200.0°C, -50…+350 °C.
  • 4-20 mA range 0…100%, display range freely adjustable.
  • 0-10 Vdc range 0…100%, display range freely adjustable.
Outputs Two relay contacts, potential-free contact N.O., max. 3 Amp @ 250VAC.
Power 24VDC connection supplied standard with power module for connection to 230VAC
Accuracy ± 1% FSR
IP-norm IP54 (front/panel side)
Dimensions Panel installation 144×96, depth 110 mm.
Options (for supplement)
  • Conversion to another measurement range, supplement per measurement input.
  • Memory card Compact-flash 32MB (incl. adapter).
  • RS232 serial cable length 2 metres.
  • Plug connecting to two RM280 data loggers.
  • Cable for connecting several data loggers via the RS485 bus, length 2 metres.
  • DCF-atomic clock receiver, which synchronises the internal clock of the data logger for applications whereby accurate time registration is important.
  • Front with transparent and lockable door.
  • USB-PCMCIA-reader for reading out the memory cards on a PC.
  • Set Line drivers for extending RS232 communication to approx. 200 metres (Excluding cable. This can be supplied at any length).
  • Regiemaster read out software with extension for automatic reading out via the computer at preset times.
  • Installed in switch box or housing for wall mounting.
  • Installed in transportable case with battery.
DOCUMENTATION

• Brochure

• Regiemaster280 Manual
• RM280 Software Manual
Connection diagram connector block

• RM280 control software Dutch version [download]
REMARK: This software is designed for Windows 98/Vista/XP only.
We cannot guarantee proper operation in newer versions Windows-7 and above.

ORDERING

The delivery of standard types from stocks and customer-specific versions can be within a few days. In view of the large number of models and options for orders you can contact our sales department< tel. +31 50-501 37 45 or by email:
sales@rstechnics.nl